• SẢN PHẨM CHẤT LƯỢNG, DỊCH VỤ CHUYÊN NGHIỆP, GIẢI PHÁP TỐI ƯU

  • flexi to stedy

  • SẢN PHẨM CHẤT LƯỢNG, DỊCH VỤ CHUYÊN NGHIỆP, GIẢI PHÁP TỐI ƯU

Online support

Hotline
0985 038 890

Newsletter

Distribution Board (DB)

Features
Electrical Characteristics
Dimensions
Download catalogue

Natural ventilation

Access panel: The door panels can either lift to access the front or the rear as request.

All metal surfaces are cleaned by chemicals (acids) and water several times before painting and final treatment with phosphate and fixatives to protect against corrosion, stable to ensure high adhesion. These parts are painted with powder coating at temperatures 200 ° C for 10 minutes to ensure the hardness of the paint surface.

Easy to operate, install, highly scalable

  • Form:                            1  to form 4.
  • Level of protection:      IP32 to IP 54.
  •  Ambient temperature:  From -50 ° C up to + 40 ° C (average of 24 hours must not exceed + 40 ° C).
  • Relative Humidity        
    • Maximum temperature +40 ° C, ≤ 50%
    • Temperature of + 20 ° C, ≤ 95%

 

 

 

Standards

IEC 61439-1,2

Class of protection

IEC 60529

Installation

In house or Outdoor

Rated Current (In)

As required

Rated insulation voltage (Ui)

1000 V

Rated operating voltage (Ue)

415/690 V. AC

Rated impulse withstand voltage (Uimp)

12 kV

Rated short-time withstand current 1 sec (Icw)

100 kA

Rated short-time withstand current 3 sec (Icw)

85 kA

Rated frequency (F)

50/60 Hz

Degree of pollution

3

Earthing diagram

TNC/TNS